    Moisture Aided Degradation of Oil Impregnated Paper Insulation in Power Transformers

    View/Open
    G26696.pdf (2.308Mb)
    Date
    2018-01-03
    Author
    Mandlik, Manoj K
    Metadata
    Show full item record
    Abstract
    Transformers are the most expensive and critical asset in any electrical power network. Their failure results in long interruption of power supply with consequent loss of reliability and revenue. Understanding and detection of the failure mechanism helps in avoiding catastrophic failures, unplanned outages and improving the power system reliability. Oil impregnated paper (OIP) and pressboards form the main soild insulation in a transformer. Life of the transformer is governed mostly by the life of OIP insulation. Until recently, it was thought that ageing of the OIP insulation in power transformer and its eventual failure, is mainly a function of temperature and electrical stresses. However, it has now been realized that the moisture causes rapid degradation of OIP and needs a special attention. Considering its practical relevance, this research program was formulated with goals: (i) to study the ageing of OIP insulation under temperature and moisture stresses, (ii) to seek correlation between diagnostic ageing indices and end-of-life (EOL) and (iii) to develop a life model for OIP considering moisture along with the thermal stress. Observing that working with actual transformers or even the prototypes are rather inordinately expensive, experiments were conducted with paper strips immersed in oil in test tubes with paper to oil ratio kept same as that in power transformers. In order to cater for the statistical nature of the phenomena, adequate numbers of test specimens were employed (25 numbers for each experiment). Experiments were conducted for two years at temperatures 90°C, 110°C & 120°C and moisture 1%, 2% & 3%. Following the literature, the degree of polymerization (DP) was chosen as the primary index for ageing. As measurement of DP is not only destructive, but also impractical on most of the working transformers, with an aim to develop suitable diagnostic indices for ageing, 2-furfural (2-FAL) and oxides of carbon (CO and CO2) were also measured. Empirical relation between ageing and amount of stresses and time have been deduced for the relevant range. Limiting value of these indices to prescribe the end-of-life, as well as, their correlation with DP have been worked out and reported. In order to bring the role of moisture explicitly, based on earlier work on multi-stress ageing, a multiplicative power law supplementing the Arrhenius factor is envisaged. Accordingly, a phenomenological combined stress model involving the time to failure, temperature, and moisture content is deduced. Based on the experimental results, this model is statistically validated and the values of parameters appearing in the model is obtained. Thus the combined stress model enables one to estimate the life of OIP insulation at any temperature and moisture under synergy. In summary, this work through experimental and analytical approach has contributed to the evaluation of the aging of OIP insulation used in power transformers under the combined action of moisture and temperature.
    URI
    https://etd.iisc.ac.in/handle/2005/2957
    Collections
    • Electrical Engineering (EE) [357]

    Related items

    Showing items related by title, author, creator and subject.

    • Studies On Silicone Rubber Nanocomposites As Weathershed Material For HVDC Transmission Line Insulators 

      Vas, Joseph Vimal (2013-06-17)
      Outdoor insulators are one of the most important parts of a power system. The reliability of a power system depends also on the reliability of the insulators. The main functions of an insulator used for outdoor applications ...
    • Studies On Epoxy Nanocomposites As Electrical Insulation For High Voltage Power Apparatus 

      Preetha, P (2016-06-21)
      High voltage rotating machines play a significant role in generation and use of electrical energy as the demand for power continues to increase. However, one of the main causes for down times in high voltage rotating ...
    • Thermal and Electrical Degradation of Resin Impregnated Paper Insulation for High Voltage Transformer Bushings 

      Jyothi, N S (2018-01-30)
      The overall reliability of a power transformer depends to a great extent on the sound operation of the bushings thereof. In view of its overwhelming advantages, resin impregnated paper (RIP) is acquiring prominence over ...

    etd@IISc is a joint service of SERC & J R D Tata Memorial (JRDTML) Library || Powered by DSpace software || DuraSpace
    Contact Us | Send Feedback | Thesis Templates
    Theme by 
    Atmire NV
     

     

    Browse

    All of etd@IIScCommunities & CollectionsTitlesAuthorsAdvisorsSubjectsBy Thesis Submission DateThis CollectionTitlesAuthorsAdvisorsSubjectsBy Thesis Submission Date

    My Account

    LoginRegister

    etd@IISc is a joint service of SERC & J R D Tata Memorial (JRDTML) Library || Powered by DSpace software || DuraSpace
    Contact Us | Send Feedback | Thesis Templates
    Theme by 
    Atmire NV